BTDIN60 - Rcbo 4P - type AC - In= 32A - Icn= 6kA - Vn= 400Vac - Idn= 30mA

BT-GN8843AC32 | 8005543458952
BTDIN60 - thermal-magnetic with earth leakage protection 4P - type AC - In= 32A - Icn= 6kA - Vn= 400 Vac - Idn= 30mA - 4 modules
Technical Characteristics
Number of poles (total) 4
Number of protected poles 4
Rated voltage 400 V
Rated current 32 A
Rated fault current 0.03 A
Leakage current type AC
Current limiting class 1
Rated short-circuit breaking capacity according to EN 61009 6 kA
Rated short-circuit breaking capacity according to IEC 60947-2 6 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1 6 kA
Frequency 50 Hz
Release characteristic C
Concurrently switching neutral conductor Yes
With interlocking device Yes
Pollution degree 2
Ambient temperature during operating (Min-Max) -25-60 °C
Width in number of modular spacings 4
Built-in depth 44 mm
Degree of protection (IP) IP20
Connectable conductor cross section solid-core (Min-Max) 1-35 mm²
Connectable conductor cross section multi-wired (Min-Max) 1-25 mm²
Width 71.2 mm
Height 88.9 mm
Depth 77.85 mm
degree of impact strength (IK) IK02
Storage temperature (Min-Max) -40-70 °C
Nominal voltage (Min-Max) 230-415 V
Electric supplying direction By the top or bottom
Terminal marking indication No
Stress test conformity (1000V) Yes
Colour Grey
RAL-number 7035
Halogen free Yes
Connection type Screwed terminal
Connection type Busbar and cable
Label space/information surface Yes
Documentation
1 documents
Technical Sheet
IDP000406EN-04 | PDF (2 MB) | EN
1 documents
Agreement
LGEGGWWDSG | FILE (519 KB) | EN · IT