Auto-protected SPD - 3P+N - Uc= 275Vac Up= 1.3kV, Imax= 10kA, In= 5kA
BT-F10HP4
|
8005543667231
Description
Self-protected Surge protective device for single-phase 230 V networks. Protection for installations whose local prospective short-circuit current (Icc) is limited to 6 kA.
Product characteristics
- IP20
- 3P+N
- Uc= 275Vac Up= 1.3kV Imax= 10kA In= 5kA
Recommendations / Restrictions
- To ensure proper protection, a lightning arrester is recommended:- at the origin of each installation (obligatory depending on the type and location of the installation to be protected,- at the origin of divisional switchboards: secondary protection or fine protection of sensitive equipment,- on all outputs of external electrical circuits (supply to secondary buildings, external lighting or external electrical panels, etc.).A communication network arrester should always be installed to protect communication equipment in the presence of lightning arresters on the low-voltage network.Translated with www.DeepL.com/Translator (free version)
Products benefits
Installation
- On 35 mm DIN rail according to DIN 35 profile or EN 60715, rails 7.5 or 15 mm deep.
Usage
- Equipped with plug-in replacement module and indicator LEDS: Green : SPD operational and Red : module needs replacing
Technical Characteristics
System configuration DC
No
System configuration IT
No
System configuration TN
No
System configuration TN-C
No
System configuration TN-C-S
No
System configuration TN-S
Yes
System configuration TT
Yes
System configuration other
No
Number of conductors (without earthing)
4
Nominal discharge surge current In (8/20)
5 kA
Max. discharge surge current (8/20)
10 kA
Degree of protection (IP)
IP20
Documentation
2 documents
Technical Sheet
IDP000018EN_05 | PDF (294 KB) | EN
Instruction Use
LE11999AA02 | PDF (234 KB)