ACB MEGABREAK MH25 draw-out 3P Frame 1 - 2500A - 65kA
BT-T813HE2500
|
8005543706879
Description
Megabreak air circuit breakers offer optimal solutions to answer to protection requirements on the origin of the low voltage electrical installation (IEC/EN 60364-1) up to 2500A.
Product characteristics
- Breaking capacity of 65kA, according to EN/IEC standard 60947-2, suitable for protection of high power industrialinstallations.
- Rated insulation voltage of 1000V. Rated impulse withstand voltage of 12kV
- Electronic protection module ot type MP2.10 (LED matrix display) or MP4.10 (LCD screen) for common for measurements and settings.Thermal and magnetic protections completely adjustable in times and currents by dedicated software
- Equipped with auxiliary contacts (2 NO/NC, expandable up to 10 and 1 fault contact), door sealing and rear terminals for horizontal connections with bars
- Can be equipped with auxiliaries (undervoltage and shunt releases, auxiliary contacts, motor operator), locking accessories and connection accessories (spreaders, rear terminals, insulation shields, interlocks)
Recommendations / Restrictions
- Must be equipped with electronic protection unit (to be ordered together for factory assembled)
Products benefits
Installation
- Can be mounted on plate in Legrand cabinets and enclosures.
Usage
- Device real-time monitoring and testing through EnerUp + Project App is possible directly from smartphone, using the MPXX02 dongle key
Advantages
- Perfectly suited for increase continuity service looking at the plant energy efficiency and in respect of “green aspects”
- The product can be configured to adapt the project needs (1:1 to 1:N), total freedom to design a proper tripping curve
- Electric and mechanical robustness, high performance, reliability and strength
Technical Characteristics
Rated permanent current Iu
2500 A
Rated voltage (Min-Max)
0-690 V
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz
65 kA
Overload release current setting (Min-Max)
500-2500 A
Adjustment range short-term delayed short-circuit release (Min-Max)
750-25000 A
Adjustment range undelayed short-circuit release (Min-Max)
5000-37500 A
Power loss
156.3 W
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Screw connection
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
2
With integrated under voltage release
No
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Complete device with protection unit
No
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP20
Documentation
2 documents
Technical Sheet
IDP001941EN/01 | PDF (3.1 MB) | EN
Instruction Use
LE12609AA | PDF (11.5 MB) | IT · EN