Conto IME

Energy meter Conto D4-Pd MID

IM-CE4DF3MTMID | 8032826514166
Conto D4-Pd MID - Energy meter, active MID (cl.B) and reactive (cl.2) Connection: direct - Network: three-phase 4-wires unbalanced - Dimension: 4 DIN modules - Output: M-bus - Current: 0.5-10(63)A - direct - Voltage: 3x230V and 3x400V - direct - Aux: self-supplied
Description

Electrical counter of active and reactive energy consumed by a three-phase circuit downstream the distribution protection. This device measures through current transformers all the electrical values of the circuit in a distribution board.

Product characteristics
  • Connection with CT up to 5A.
  • Communication: MBus output.
  • Double tariff or Pulse input to collect other meter (gas, water, electrical meters).
  • MID Certified.
  • Bidirectional measure of production and consumption energies.
Products benefits
Installation
  • Easy connection of communication thanks to removable connectors. One input connector for double tariff or Pulse input to collect water or gas meters without using added concentrator device.
Usage
  • Backlit display and simple access to easy reading of data. Pre-visualization of parameters. Settings mode protected by user code Bidirectional measure of production and consumption energies
Advantages
  • Measure of run hours on each tariff.
Technical Characteristics
Type of meter Electronic
Nominal current (In) 5 A
Max. current (Imax) 63 A
Nominal voltage (Un) N-L (Min-Max) 197-265 V
Nominal voltage (Un) L-L (Min-Max) 340-460 V
Frequency (Min-Max) 49-61 Hz
Accuracy class B
Pole type Three conductor/four conductor
Model Direct measurement
Energy type Effective power and reactive power
Suitable for Purchase/supply
Tariff type Two-tariff
Tariff control External
Measurement type load profile No
Escapement mechanism Yes
Calibrated Yes
Approval Measuring Instruments Directive
Pulse output None
Type of indication Digital
Mounting method DRA (DIN-rail adaptor)
Width in number of modular spacings 4
Width 71.2 mm
Depth 66 mm
Height 92.4 mm
Type of interface M-bus (wired)
With lock code Yes
Number of positions total (counter) 9
Degree of protection (IP) IP54
degree of impact strength (IK) IK08
Operating / setting temperature (Min-Max) -25-55 °C
Storage temperature (Min-Max) -25-70 °C
Voltage type AC
Terminal marking indication Yes
Colour Grey
RAL-number 7035
Halogen free Yes
Prewired No
Connection type Screwed terminal
Terminals capacity (Min-Max) 1-16 mm²
Label space/information surface No
Connected object No
Documentation
7 documents
Technical Sheet
IDP000190_04 | PDF (3.3 MB) | DE · IT · FR · EN
Technical Sheet
IDP000190EN_04 | PDF (4.6 MB) | EN
Technical Sheet
IDP000190FR | PDF (850 KB) | EN · FR
Technical Sheet
IDP000385_IM-CE4DF3MTXXX-IM-CE4TBMTXXX | PDF (341 KB) | EN
Technical Sheet
IDP000385FR | PDF (255 KB) | EN · FR
Instruction Use
LE11297FR | PDF (2.6 MB) | EN · FR
Instruction Use
LE11299FR | PDF (2.1 MB) | EN · FR
1 documents
PEP-EPD
LGRP-01746-V01.01-EN | PDF (908 KB) | EN
1 documents
Catalog Commercial Page
3226373 | PDF (16.9 MB) | EN