M2 250B - thermal-magnetic Mccb with residual current protection 3P+N/2 - Icu= 25kA - In= 200A

BT-T724B200D | 8012199989389
M2 250B - thermal-magnetic with earth leakage protection 3P+N/2 - Icu= 25kA - In= 200A
Technical Characteristics
Rated permanent current Iu 200 A
Rated voltage (Min-Max) 220-690 V
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz 25 kA
Overload release current setting (Min-Max) 160-200 A
Adjustment range short-term delayed short-circuit release (Min-Max) 1000-2000 A
Adjustment range undelayed short-circuit release (Min-Max) 1000-2000 A
Device construction Built-in device fixed built-in technique
Integrated earth fault protection Yes
Type of electrical connection of main circuit Screw connection
Suitable for DIN rail (top hat rail) mounting Yes
DIN rail (top hat rail) mounting optional Yes
Number of auxiliary contacts as normally closed contact 1
Number of auxiliary contacts as change-over contact 1
With switched-off indicator Yes
With integrated under voltage release Yes
Number of poles 4
Position of connection for main current circuit Front side
Type of control element Wing knob
Complete device with protection unit Yes
Motor drive integrated No
Motor drive optional Yes
Degree of protection (IP) IP30
Contains Batteries and/or Accumulator Yes
IEC code (Pack1) CR1616
Battery ou Accumulator (Pack1) Battery (not rechargeable)
Element Composition (Pack1) Lithium (battery or accumulator)
Number of Pack 1 2
Number of Single Element (Pack1) 1
Single Element weight (Pack1) 1.1 g
Pack1 Location Product includes a battery
Regulation Type (Pack1) P : Portable (Standard format)