SPD - 3P+N T1+T2 Imax=8KA - T2 Imax 60kA
BT-F10LB4
|
8005543546208
Description
The BTICINO lightning arrester is a device that prevents damaging equipment due to lightning. It is also equipped with overload and short circuit protection.Suitable for domestic and small tertiary installation.
Product characteristics
- 20kA
- 400V
- 4 modular spacing
Recommendations / Restrictions
- "To provide correct protection, a lightning arrester is recommended:- at the origin of each installation (mandatory depending on the type and location of the installation to be protected,- at the origin of divisional switchboards: secondary protection or fine protection of sensitive equipment,- on all outputs of external electrical circuits (supply to secondary buildings, external lighting or external electrical panels, etc.).A communication network arrester should always be installed to protect communication equipment in the presence of a lightning arrester on the low-voltage network."
Technical Characteristics
System configuration DC
No
System configuration IT
No
System configuration TN
No
System configuration TN-C
No
System configuration TN-C-S
No
System configuration TN-S
Yes
System configuration TT
No
System configuration other
No
Number of conductors (without earthing)
4
Nominal discharge surge current In (8/20)
20 kA
Nominal voltage AC
400 V
Max. continuous voltage AC
320 V
Voltage protection level
1.7 kV
Integrated backup fuse
No
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
4 modular spacing
Max. conductor cross section solid (solid, stranded)
35 mm²
Max. conductor cross section flexible (fine-strand)
25 mm²
With remote signalling contact
No
Signalling at the device
Optical
Category type 2
Yes
Degree of protection (IP)
IP20
Documentation
3 documents
Technical Guide
EXB20026 | PDF (8 MB) | EN
Technical Sheet
IDP000062EN_01 | PDF (677 KB) | EN
Instruction Use
LE07622AA | PDF (413 KB)
1 documents
PEP-EPD